Quick Start
Getting Started
Adjust menu items (skip steps where default values are ok)
1) Select °F or °C
default= °F
Press "MENU" 2 times until 'CHFC' appears.
Press "ENTER".
Press "MENU" to switch between °F or °C. When desired scale is displayed press enter.
2) Select 1 or 2 zones default=2
Press "MENU" 9 times until '1Or2' appears.
Press "ENTER".
Press"1" for 1 zone.
Press "2" for 2 zones.
Press "ENTER".
Press "MENU" 10 times until 'FAIL' appears.
Press "ENTER".
Press "1" to switch between 'OFF' and 'HEAt'.*
When desired operation is displayed press "ENTER".
*When 'HEAt' is selected the heater will cycle on 15 min and off 15 min if a thermistor fails. 'OFF' will keep all outputs off if a thermistor fails.3) Select thermistor fail mode
default=off
4) Adjust clock
Press "CLOCK". Adjust time with # keys. Note: 24 hr. clock format
Press "ENTER".5) Set start times and target temperatures for DIF, DAY, and NITE stages. default settings:
Stage Start Time Zone 1 °F Zone 2 °F DIF 6:00 65 65 DAY 8:00 65 65 NITE 17:00 65 65
Press the DIF, DAY, or NITE key, the start time for that stage appears (24 hr. clock format). Adjust the start time - DIF must start earlier than DAY, and DAY must start earlier than NITE.
Press "ENTER" - '°F 1' appears.
Adjust Zone 1 target temperature (32 - 131 °F).
Press "ENTER" - '°F 2' appears if set to 2 zones, else adjustment complete.
Adjust Zone 2 target temperature (32 - 131 °F).
Press "ENTER".
Adjustments, Options and Overrides
A) Adjust step offset from target temperature.
Press "HEAT" or "COOL" output keys until 'AUtO' appears.
Press "ENTER"-output name and step offset will appear. Adjust offset with # keys (allowed values 0-31).
Press "ENTER".B) Output manually "off"
Press output key until 'OFF' appears.
Press "ENTER".C) Ouput manually "on"
Press ouput key until 'On' appears.
Press "ENTER". The ouput will stay on for the programmed amount of time in the menu 'OtOA' (on-to-auto) timer and then switch to 'AUtO'.D) Temporarily override target temperature
Press "4" or "7" to adjust Zone 1 and "6" or "9" to adjust Zone 2.
Press "ENTER".E) Manually run programmed
vent cycle
Press "VENT".
Press "CLOCK".
Press "5", the zone indicator on the left of the display will switch to the new zone. F) Manually run programmed
timer cycle
Press "TIMER".
Press "CLOCK"G) View temperature in other zone (2 zone only) H) View output status
Press "8", a bar will be displayed for each ouput that is activated. Statistics
Reset Min and Max
Press 2
Display minimum temperature since last reset
Press 1
Display maximum temperature since last reset
Press 3
Display average temperatures
Press "0" (stats) until the desired day appears-Day 1 is today, Day 2 is yesterday...
Press "ENTER", the average temperature for the DIF stage appears.
Press "ENTER", the average temperature for the DAY stage appears.
Press "ENTER", the average temperature for the NITE stage appears.
Press "ENTER", the average temperature for the 24hr. period, DIF-NITE, appears.
Press "ENTER".